Enclosure
Testing Summary - Aberdeen Proving Grounds |
|
Test |
Requirement |
Result |
Data |
|
Blast |
60 PSI - 117 ms
Overpressure |
PASSED |
71 PSI at
distance of 12' 8" - Zero structural or visual damage |
|
Ballistic |
NIJ IV - 7.62
APM2 at 2850 FPS; 12" Spacing |
PASSED |
Stopped 5 shots
in 4" square at 2900 FPS (See images below) |
|
Fragment
Simulated Projectile |
None |
PASSED |
Stopped 20mm FSP
at 3800 FPS |
|
Forced Entry |
30 Minutes |
PASSED |
52 min to breach
door using 4-ton "come along"; unable to breach w / chop
saw; unable to penetrate w / hand tools |
|
Fire / Heat |
Thermal
Radiation - Blast; No flame penetration of 2Mw Crib
Fire 30 minutes |
PASSED |
No flame
penetration 1400° F after 30 minutes; 11° F increase at
inside wall surface after 30 minutes |
|
Roof Load |
14Tn / 300 Ft²
- 4Tn / 100 Ft² |
PASSED |
No buckling or
damage |
|
Hurricane Force
Wind Loads |
2 Hrs -
Sustained Winds - 75MPH / 100MPH |
PASSED |
No structural or
visible damage |